Installation Procedures: Connect an Emergency Power Off Switch
20 InfraStruXure System—Installation and Start-Up
3. Test the EPO switch to ensure that it is wired and working correctly:
a. Place the Arm/Test rocker switch in the Tes t position. The EPO state LEDs will be off and
the PDU display interface will show the following alarm (in addition to any other active
alarms):
b. Engage the EPO switch. (If your switch is momentary, engage it with one person watching
the EPO state LEDs, and another at the EPO switch.)
c. Observe the EPO LEDs. If the switch is wired and working properly, when the switch is
engaged, both of the EPO state LEDs are red.
d. If the test was successful, place the Arm/Test rocker switch back to the Arm position. The
PDU display interface will clear the EPO test mode alarm. If the test was not successful, see
the troubleshooting chart:
e. Repeat this test for each EPO switch installed.
4. Ensure that the Arm/Test rocker switch is in the Arm position on the monitoring unit.
Problem Action
Neither state LED was red when
EPO switch was engaged
Check the wiring to your EPO switch.
Check to make sure the EPO DIP switch
configuration is correct for your switch
(NO or NC). See step 2 on the previous page for
proper configuration instructions.
Only one of the state LEDs was
red when EPO switch was
engaged
Check to make sure the EPO DIP switch
configuration is correct for your switch
(NO or NC) and test again. See step 2 on the
previous page for proper configuration
instructions.
If the switch is configured correctly and both
LEDs are not red after testing again, contact
customer support at a number on the back cover
of this manual.
EPO Ready To Test
Active Alarm xxofxx