– User Manual 34003676EN/BB Page 46/76
Name and status of each contact can be configured
Recording of events and measurements in the card log
Possibility of shutting down the installation safely if one of the thresholds is exceeded or if a dry contact
closes
Connection to the Network Management Card by CAT5 straight RJ45 network cables (maximum
card/sensor distance: 20m)
3.6.2 Environment status
For both measurements, a graduated gauge proposes the following functions:
The cursor indicates the current value.
Two red zones to the left and right represent the high and low thresholds that can be set on the Environment
Settings page.
When the measured value enters one of these zones, a alarm can be notified (see Notification parameter in
the Environment Settings page).
Time-stamped minimum and maximum temperatures show the extreme values recorded since the last Reset
Min/Max, a thin dotted line shows their positions on the gauge.
Min and Max can be forced at any time to the current value by clicking on the Reset Min/Max button.
Calibrate: the sensor is calibrated in the factory, but the user can apply an offset to adjust the measurement.