www.mgeups.com
Network
Management Cards
User Manual
THE UNINTERRUPTIBLE POWER PROVIDER
Network Management Card
– User Manual 34003676EN/BB Page 62/76
5 Configuration in local mode and via Telnet
5.1 Configuration in local mode
◗ Use the cable supplied with the card.
◗ Connect the card to a computer equipped with a hyper-terminal type emulator. The serial link should be set
at 9600 bauds, 8 bits, no parity, 1 stop bit and no flow control.
◗ Check that UPS power is on.
◗ A few seconds after terminal opening, press the "Enter” button. The menu asks you to enter your password
(MGEUPS by default), and then press “Enter”.
◗ The card will disconnect itself after 3 minutes of inactivity.
◗ The menu is in English only.
+===========================================================================
+
| [ MGE UPS SYSTEMS SNMP/Web agent Configuration menu ] |
+===========================================================================
+
Enter Password: ******
+===========================================================================
+
| [ MGE UPS SYSTEMS SNMP/Web agent Configuration menu ] |
+===========================================================================
+
1. Agent Configuration
2. UPS Parameters
3. Access Control Table
4. Reset Configuration To Default
5. Reset Agent
0. Exit
Please Enter Your Choice =>