Network Management Card
– User Manual 34003676EN/BB Page 51/76
4.1.1.2 Initiating the shutdown procedure when the battery level is lower than: (if capacity under)
When the card detects that the remaining backup time percentage is less than the configured level, the
shutdown sequence is started.
By default, this value is set in the UPS.
Note:
Certain types of UPS only accept pre-defined minimum battery level values (e.g. : 20% or 40% for COMET and
PULSAR EXtreme). Check the UPS documentation.
4.1.1.3 Shutdown when backup time is less than
When the Network Management Card detects that the percentage of backup time remaining is less than the
value set, the shutdown sequence is started.
4.1.1.4 Shutdown duration
Duration required for the systems protected by the Shutdown Modules to shut down (in seconds).
4.1.2 Specific set-up for long autonomy installation (> 30 mn)
On installation where the backup period is longer than 30 minutes, the Network Management Card will initiate
automatically a shutdown at the end of the shutdown timer, to avoid that, the shutdown timer must be
programmed to a value higher than the real autonomy.
4.1.3 Controlled outlets
Some UPS models are equipped with outlets (typically 2), that can be controlled individually (while still
remaining dependent on the main UPS control).
Shutdown of the main outlet systematically causes shutdown of the programmable outlets.
Depending on the UPS range, the following notation is used to mark these outlets:
Main outlet: Main or 1
Programmable outlet 1 1 or 2
Programmable outlet 2 2 or 3
4.1.4 Connecting a server protected by UM-Client to a programmable outlet
Only UM-Client is compatible with the programmable outlets, the Network Shutdown Module will be compatible
with release 3.0.
After connecting the server electrically to one of the controlled outlets, UM-Client must be informed of the outlet
number to which it is connected.