Network Management Card & Modbus/Jbus 34022321XT indice :AD Page 16/91
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com
Ethernet port
LED Colour Activity Description
ACT Green Off Card not connected to the network.
On
Card connected to the network but
without activity
Flashing
Port is active in receiving /
transmission
100M Orange Off Port operating at 10Mbits/s.
On Port operating at 100Mbits/s.
Service port (Settings/Sensor)
LED Colour Activity Description
UPS Green Off Card startup in progress.
Data On Communication with UPS in progress
Flashing
Normal operation.
Communication with the UPS is
operational
RS232 Orange Off Configuration menu is active
On Normal operation. Configuration
menu is deactived
Flashing Communication with the Environment
Sensor (option).
Phone port
LED Colour Activity Description
UPS Green Off Card not connected to phone network
Data
On
Card connected to phone network,
but no activity
Flashing Port is sending/receiving
CD Orange Off Modem is not connected
On Modem is connected
Flashing Modem is connecting
4.3 Installation in the UPS
The Network Management Teleservice Card (66124) can be "hot" installed in the MGE Galaxy 7000 UPS or SSC unit.
Note the card's MAC address prior to insertion
Connect the ETHERNET cable
Insert and tighten the card's retaining screws
Wait 3 min.; the card is completely operational when the green UPS Data LED flashes continuously
For Teleservice installation, the NMTC card must be installed in the SSC unit.
4.4 Sensor installation (option)
The Environment sensor is available as an option on the Network Management Card. SKU number is 66846.
The sensor allows remote monitoring of the UPS's environment through regular measurements: temperature, humidity, status of two external
contacts. It also enables notification of alarms (e-mail, trap SNMP) according to pre-programmed thresholds.
Page view 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 90 91

Comments to this Manuals

No comments