Network Management Card & Modbus/Jbus 34022321XT indice :AD Page 56/91
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com
7 Server protection
7.1 Set-up of the shutdown parameters
The Network Shutdown Module, on protected server boot, subscribes itself automatically to
notified applications list and sends its essential
data:
IP Address or hostname of the server on which it is installed: So that the card can inform it of power events.
Time required to shutdown the server (Shutdown Duration, configurable in the "Set-up" menu of each NSM): The card takes into account the
longest shutdown time of all the Network Shutdown Modules subscribed (This is the Shutdown duration of the
Shutdown parameters) page
to manage UPS shutdowns without affecting any of Shutdown Modules connected.
During normal operation, the Network Shutdown Module periodically checks its connection with the card.
In case of a major power event, the card sends information to the Network Shutdown Module which reacts according to the situation.
(shutdown order, programmed actions, messages to the administrator and to users via the network)
When the server shuts down, the Network Shutdown Module unsubscribes itself from the
notified applications.