Communication Cables: Communication Cables in Installations without PDU-XR
10 Symmetra PX 160 kW 400 V Installation 990-3017A-001
Route the communication cable from the last XR Battery Enclosure in the row to the UPS XR
communications port 2.
Route the battery breaker trip cable from the last XR Battery Enclosure to the EPO/ancillary
interface board (0P4123) and plug it into the J27 connector.
Install the communication cables from the Maintenance Bypass Panel into the maintenance bypass
interface board (0P4194). Refer to the wiring diagram on the next page for more information.
Front of the UPS
XR communication cable
Battery breaker trip cable (EPO)
MBP communication cable
Front
Top view
UPS Maintenance
Bypass Panel
XR Battery
Enclosure
XR Battery
Enclosure
XR Battery
Enclosure
XR Battery Enclosure UPS Maintenance Bypass Panel
XR Battery
Enclosure