Power Cables: UPS Input and Output Cables in Installations without PDU-XR
990-3017A-001 Symmetra PX 160 kW 400 V Installation 33
Single mains installation—top or bottom cable entry
Note: As the neutral from AC mains input and AC bypass input is hardwired internally in the
UPS, it is not necessary to install a jumper between the two neutral connections in single mains
installations.
Note: Install the PE cable in the UPS according to the symbol on the grounding rail.
Caution: Ensure clockwise phase rotation and neutral location. The power terminal bolt
diameter is 10 mm. The required torque value is 26 Nm.
Run the cables through top or bottom of the enclosure and mount the cables to the busbars
according to the labels.
Install the three cables (0W3617) included with the unit.
Neutral
Mains L2
Mains L1
Mains L3
Neutral
Bypass L2
Bypass L1
Bypass L3
Mains
Back of the UPS
Output
PE
PE