APC SYMMETRA PDUM160H-B Specifications Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
16 Symmetra PX 160 kW 400 V Installation 990-3017A-001
Battery Cables
How to Install the APC Battery Solution
The Symmetra PX 160 kW UPS can monitor up to three APC XR Battery Enclosures in systems with
PDU-XR and up to four APC XR Battery Enclosures in systems without PDU-XR.
Note: In installations with non-apc batteries, follow the documentation provided with the
batteries.
How to connect the battery cables in the XR Battery Enclosure
Remove the four bolts from the upper cover plate and remove the plate (only in top entry systems).
Remove the four bolts from the lower cover plate and remove the plate.
Take the cables included in each XR Battery Enclosure. Remove the cable lugs from the cables that
will be used to connect the XR Battery Enclosures. For the cables that connect to the UPS, cut off
only the cable lug on the end that will be mounted in the XR Battery Enclosure.
Back of the XR Battery Enclosure
Back of the XR Battery
Enclosure with plates removed
Page view 19