USER’S GUIDE
Battery Management System
47
SNMP
An Access option (Settings in the control console) enables (by default) or
disables SNMP. When SNMP is enabled, the Access Control settings
allow you to control how each of the four available SNMP channels is used.
To define up to four NMSs as trap receivers, see Trap Receivers;
to use SNMP to manage a UPS or an environmental monitor, see
the PowerNet
®
SNMP Management Information Base (MIB)
Reference Guide (.\doc\en\mi/jointfilesconvert/96925/bguide.pdf) on the APC Battery
Management System Utility CD.
Setting Definition
Community
Name
This setting defines the password (maximum of 15 characters) which an
NMS that is defined by the NMS IP setting uses to access the channel.
NMS IP/
Domain
Name
Limits access to the NMS specified by a domain name or to the NMSs
specified by the format used for the IP address:
• A domain name allows only the NMS at that location to have access.
• 159.215.12.1 allows only the NMS with that IP address to have access.
• 159.215.12.255 allows access for any NMS on the 159.215.12 segment.
• 159.215.255.255 allows access for any NMS on the 159.215 segment.
• 159.255.255.255 allows access for any NMS on the 159 segment.
• 0.0.0.0 or 255.255.255.255 allows access for any NMS.