APC SU1400XLT User Manual Page 110

  • Download
  • Add to my manuals
  • Print
  • Page
    / 115
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 109
CMD DFO RSP FSZ FVL
u D 4 3 127 130 133 136
u M 4 3 229 234 239 224
u A 4 3 108 110 112 114
u I 4 3 253 257 261 265
l D 4 3 106 103 100 097
l M 4 3 177 172 168 182
l A 4 3 092 090 088 086
l I 4 3 208 204 200 196
e 4 4 2 00 15 50 90
o D 1 3 115
o J 1 3 100
o I 1 3 230 240 220 225
o M 1 3 208
s 4 4 1 H M L L
q 4 4 2 02 05 07 10
p 4 4 3 020 180 300 600
k 4 4 1 0 T L N
r 4 4 3 000 060 180 300
E 4 4 3 336 168 ON OFF
CMD == UPSlink Command.
u = upper transfer voltage
l = lower transfer voltage
e = return threshold
o = output voltage
s = sensitivity
p = shutdown grace delay
q = low battery warning
k = alarm delay
r = wakeup delay
E = self test interval
DFO == (4)-all-countries (D)omestic (I)nternational (A)sia (J)apan
(M) North America - servers.
RSP == Total number possible answers returned by a given CMD.
FSZ == Max. number of field positions to be filled.
FVL == Values that are returned and legal.
Programming the UPS EEPROM
There are at this time a maximum of 12 different values that can be programmed into the UPS EEPROM.
They are:
Command Meaning
c The UPS Id or name
x The last date the batteries were replaced
u The Upper Transfer Voltage
l The Lower Transfer Voltage
e The Return Battery Charge Percentage
o The Output Voltage when on Batteries
s The Sensitivity to Line Quality