APC SU1400XLT User Manual Page 52

  • Download
  • Add to my manuals
  • Print
  • Page
    / 115
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 51
4. Matrix-UPS and Smart-UPS recalculate the runtime-related parameters every time the UPS goes on
battery.
When doing a runtime calibration with "older" batteries, APC Technical Support recommend doing a
complete discharge and recharge first.
If you have "dumb" UPS (aka simple signalling) like a Back-UPS, then your only option is to do a manual
runtime calibration.
"Manual" Runtime Calibration
Most of the information in this section is taken from APC's website. Any non-APC additions have been
inserted in square brackets.
For a "smart" or "smart signalling" Back-UPS Pro or Smart-UPS:
Perform a Runtime Calibration. This is a manual procedure and should not be confused with the
runtime calibration performed through PowerChute plus [or apctest]. The batteries inside of the
Smart-UPS are controlled by a microprocessor within the UPS. Sometimes it is necessary to reset
this microprocessor, especially after the installation of new batteries. Stop the PowerChute plus [or
apcupsd] software from running and disconnect the serial cable. There must be at least a 30% load
attached to the UPS during this procedure, but the process will cause the UPS to shut off and cut
power to its outlets. Therefore, attach a non-critical load to the UPS and then force the UPS on
battery by disconnecting it from utility power [suggest not disconnecting, but simply turning off utility
power thereby preserving earthing]. Allow the unit to run on battery until it turns off completely. Make
sure a 30% load is present! Plug the UPS back into the wall outlet [switch utility power back on] and
allow it to recharge (it will recharge more quickly turned off and with no load present). Once the unit
has recharged, the "runtime remaining" calculation should be more accurate. Remember that if the
unit is an older model, then the runtime will not improve significantly.
Background:
An APC Smart-UPS has a microprocessor which calculates runtime primarily based on the load
attached to the UPS and on its battery capacity. On the right side of the front display panel there is a
vertical graph of five LEDs. Each LED is an indication of battery charge in increments of twenty
percent: 20, 40, 60, 80, 100% (bottom to top). For example, if the battery charge is 99%, then only
four of the five LEDs are illuminated.
To ensure that an operating system receives a graceful shutdown when using PowerChute plus or a
SmartSlot accessory, an alert is generated by the Smart-UPS indicating that the UPS has reached a
low battery condition. The alert is audible (rapid beeping), visual (flashing battery LED or LEDs), and
readable through the graphical interface of PowerChute plus software (or a native UPS shutdown
program within a particular operating system.) In order to calculate this "low battery condition," all
Smart-UPS products have a preconfigured low battery signal warning time of two minutes (this is the
factory default setting). There are a total of four user-changeable settings: 2, 5, 7, or 10 minutes. If
the low battery signal warning time is set for 2 minutes, then the alerts will activate simultaneously
two minutes prior to shutdown. Similarly, if the total runtime for a particular UPS is 30 minutes with a
low battery signal warning time set at 10 minutes, then the UPS will run on battery for 20 minutes
before the low battery alert begins.
Total runtime is primarily based on two factors, battery capacity and UPS load. UPS load and runtime
on battery are inversely proportional: as load increases, battery runtime decreases and vice versa.
When utility power is lost, the UPS begins discharging the battery in order to support the attached
load. Once power returns, the Smart-UPS will automatically begin to recharge its battery.
For a Matrix UPS:
It is unnecessary to subject a battery bank to an excessively long calibration. Remove battery packs
or increase the load (space heaters are good dummy loads) to obtain a reasonable time length for the
calibration (under an hour if possible).
At the start of a calibration, the Matrix microprocessor saves the Estimated Run Time displayed.
Page view 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 114 115

Comments to this Manuals

No comments