Page view 15
Operation: Operation Procedures
12 Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001
Press Initiate Transfer.
Verify that the status in the upper right corner of the
screen has changed to Static bypass.
How to transfer from static bypass to normal operation
Press the Operation button on the UPS Summary
screen.
Press the Static Bypass -> Online button. Press
inside the password field and type in the user
password using the keyboard on the screen.
Complete with Enter.
Press Initiate Transfer.
Verify that the status in the upper right corner of the
screen has changed to Normal.
Page view 15