APC AP95500 Datasheet Page 152

  • Download
  • Add to my manuals
  • Print
  • Page
    / 300
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 151
You access the display from the right-click menu in the Device Alarm Configuration view
or the Navigation view in the Alarm Configuration perspective.
When you access the display from the Navigation view, all the device alarms associated
with the device groups or devices selected are configured simultaneously.
When you access the display from the Device Alarm Configuration view, you can specify
which device alarms associated with the device groups or devices you selected in the
Navigation view to configure. You can expand the selection to view and configure device
alarms by alarm type, alarm name, or by one or more devices reporting that alarm.
Note: With the exception of the Enabled option, device alarm settings you modify do not
apply to active alarms. The modified settings will apply the next time the alarm is triggered.
Element Description
Enabled
Select to enable the device alarm, if it is disabled.
Note: Device alarms are enabled by default.
Severity
Select the severity you want associated with the
device alarm: Information, Warning, Error,
Critical, or Failure.
Description
The alarm description provided by the device.
You cannot modify this description.
Custom Description
Provide a description you want included in the
device alarm notifications.
Recommended Action
The recommended action provided by the
device. You can modify the recommended action
to include instructions you want in the device
alarm notifications.
Reset to default
Reset the recommended action to default, if it has
been modified.
Button icons (Device Alarm Configuration view)
In addition to standard minimize and maximize icons, two icons are available to perform
specific Device Alarm Configuration view functions.
Icon Description
Use this Configure Columns icon to
identify the attribute columns that appear in
the Device Alarm Configuration view.
Use this Filter Device Alarms icon to
enable filters that prevent device alarms
with 'Enabled' set to 'No', and device alarms
of any severity, from appearing in the list.