APC AP95500 Datasheet Page 170

  • Download
  • Add to my manuals
  • Print
  • Page
    / 300
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 169
the “yes” and “no” values and
the macro is translated, if the
alert is still active the word
"active" would appear and when
it has returned to normal, the
word "cleared" would appear.
${USERURL} The user-specified URL that
can be defined within the
threshold configuration.
http://www.mysite.com
${USERDESC} The user-specified description
value which can be defined
within the threshold
configuration.
“Too high”
${START_TIME} The time at which the alarm
condition was initially detected.
13:01:45
${RESOLVE_TIME} The time at which the alarm
condition returned to normal.
13:07:13
${SENSORLUID} The locally unique ID of the
sensor generating the alarm.
TEMP1
${SENSORGUID} The globally unique ID of the
sensor generating the alarm.
B000113_TEMP1
${EVENTID} The unique 16 character
identifier shared by all
messages generated as a result
of a single alarm notification
event. For example, if an
appliance generates an alarm
notification when the internal
temperature sensor threshold is
exceeded, and then generates
a "return to normal" message
when the temperature drops
below the high threshold, both
of these messages will have the
same Event ID number.
However, if the temperature
rises again and a second
threshold exceeded alarm is
generated, the second alarm
will have a new Event ID.
3E4512C0FE03440F
${DEVICELABEL} The label of value of the device
that either contains the sensor
that reported the alarm or to
which the sensor is connected.
My Device
${ALERTPOD} The label of value of the pod that
either contains the sensor that
reported the alarm or to which
the sensor is connected.
My Pod
${ALERTPODSERIAL} The serial number of the pod
that either contains the sensor
that reported the alarm or to
which the sensor is connected.
NB007100730114
${ALERTPORT} The label value for the external
sensor port to which the
external sensor that reported
the alarm is connected.
Ext1
StruxureWare Central 6.3.0
170
Page view 169
1 2 ... 165 166 167 168 169 170 171 172 173 174 175 ... 299 300

Comments to this Manuals

No comments