SNMPv1 Agent
Configured as an
SNMPv1agent by default.
Can be configured as an
SNMPv1 agent, disabled by
default.
SNMPv3
Not supported Supported
SOCKS 5 Proxy Access
One user Any user
Server Proxy
Enable/disable only Enable, with an option to
disable on addresses you
specify, and disable.
FTP Settings
Manage File Transfer Protocol
(FTP) or Secure Copy (SCP)
access values for APC SNMPv1
and SNMPv3 devices.
General Timeout
No longer required. Configured
on individual SNMP devices.
Event Log
No longer available. Replaced
by Alarm History view.
Significant Differences
Product Updates: Product updates for the StruxureWare Central server require a
support contract. You must contact APC Support to get the URL for the update file, then
use the StruxureWare Central client to perform the update.
Localization: The StruxureWare Central server and client are localized to ten languages.
BMS Support: The StruxureWare Central server requires a license key to enable
Building Management Systems (BMS) support. Port 502 is used to connect a BMS to the
MODBUS TCP Output Module. Direct serial connection via MODBUS RTU is not supported.
The BMS registers are remapped, with many values using a different scale. For example,
in InfraStruxure Manager, divide value by 100; in StruxureWare Central , divide value by
10. Additionally, register maps can be customized.
Notification: Alarm notification is not a separately-licensed StruxureWare Central server
feature.
The Alarm Configuration perspective provides options used to configure how the
StruxureWare Central server reports alarms and threshold violations, and manages alarm
actions, for monitored SNMP and MODBUS devices.
Notification policies replace the escalation policies available in InfraStruxure Manager, with
a significant difference: the ability to escalate and acknowledge alarms is not available.
Note: Alert notification for monitored NetBotz Appliances is configured in NetBotz
Appliance Configuration, a Device menu option.
Reports: Rather than the thirteen pre-defined reports available in InfraStruxure Manager,
the Reports perspective in the StruxureWare Central client provides five pre-defined
snapshot reports, eighteen sensor-specific sensor history reports, and the ability to create
custom sensor history reports. The Reports perspective allows you to do the following:
Generate and view snapshot reports and sensor history reports.
View sensor history report data in graph-format, summary-format, or table-format.
Save sensor history reports and the report criteria.
Configure export actions, such as email, FTP, HTTP, NFS, and Windows share.
StruxureWare Central 6.3.0