–19–
How MasterSwitchplus Works
Graceful Shutdown Sequence for Environment Alarms
.
Power On Delay†
Remain Off Delay
Outlet is turned on
Environmental Monitor asserts alarm
Environmental Monitor clears alarm
Server confirms shutdown
Power Off Delay† expires
Outlet is turned off
UPS is operating on AC power
UPS exceeds Battery Capacity Threshold†
or
YouissueBatteryCapacityThresholdOverridecommand
Outlet remains off
Youissuea
Cancel
command
Power On
Delay expires
Is there a cable connected to the Basic Port?
No
Ye s
Device Confirm†
Ye s N o
Does the configuration contain a UPS?
No Yes
MasterSwitch plus asserts
AC Fail and Low Battery signals
Is the alarm still active?
Ye s N o
Alarm Action Delay† expires
This diagram sequences the events
that an outlet set to Graceful Shutdown
will follow when your Environmental
Monitor issues an alarm. The
sequence is an unattended operation
that requires you to choose values for
the following properties:
• Alarm Action Delay
• Device Confirm
• Power Off Delay
• Battery Capacity Threshold
• Power On Delay
Unit Property‡
Outlet Property†
Shutdown
Restart