11Symmetra MW II with Internal Bypass Static Switch - Operation - 990-1756C-001
4. The UPS Start-Up screen appears with the Charge DC
Capacitors step highlighted. Follow the procedure on
the screen which is specific to your system.
5. Verify that the status in the upper right corner has
changed to Normal.
How to transfer from normal to static bypass operation
1. Press the Operation button on the UPS Summary
screen.
2. Press the Online -> Static Bypass button. Press inside
the password field and type in the user password using
the keyboard on the screen. Complete with
ENTER.