Route 120 VAC power wiring from service switch to ECR
AR822-II and attach to 120 VAC power terminals.
Route 120 VAC power wiring from junction / switch
box to ECR ARM-6P (or AZ-6CP or ARH-3). Wiring can
be routed through ½” offset nipple connector and into
control module enclosure. Connect 120 VAC power
wiring to 12 VDC power supply’s pig tail in control
module using wire nuts, attach ground wire to control
module enclosure grounding screw located inside
bottom of enclosure. Figure 12-3.
Wire control module to zone relay control and AR822-II
following appropriate
freewatt PLUS
System low voltage
and line voltage electrical schematics.
Wire circulators and MCHP’s hydronic pump to zone relay
control and AR822-II following instructions found in their
installation manuals and
freewatt PLUS
System electrical
schematics.
Connect MCHP Coolant Pump’s 24VDC power cable to system
controller.
Connect 24 VAC circuits between boiler control and
freewatt
Control Module per applicable electrical
schematic.
Con gure jumper on control module circuit board (Figure
12-4) for set-up of hydronic system water heating and
space heating zones. Install jumper on DHW pins if zone 1 is
connected to aquastat in indirect water tank. Install jumper
on HEAT pins If zone 1 is connected to thermostat for space
heating. Zone 1 input on the
control module must be used
for indirect water heater if indirect water heater is used with
freewatt PLUS
System.
Connect Coolant Pump in HI Module to Control Module J04
connector using furnished coolant pump cable.
12.6 ECR Zone Relay Controls
Install appropriate ECR Zone Relay Control for temperature
control of different heating zones and accommodation of
indirect water heater (if used). Refer to Electric Schematics
for speci c wiring details.
Use ECR ARM-6P control for
freewatt PLUS
Systems
zoned with circulators ARM-6P control will accommodate up
to six zones. Expand ARM-6P with additional ARM controls if
more zones are needed.
Use six-zone ECR AZ-6CP For
freewatt PLUS
System’s
zoned with valves. AZ-6CP can be expanded up to ten zones
with water heating priority with additional AZ control.
Use three zone ECR ARH-3 control, expanded with additional
ARH controls for
freewatt PLUS
Systems with air
handlers (hydro-air).
DHW priority dipswitch on zone control applies only in
bypass mode. DHW priority in MCHP mode is determined
by rmware setting in freewatt control module accessible
via MINT software. Default setting is priority ON when DHW
enabled.
Figure 12-4 Control Module Con guration DHW or
CH Jumper
Figure 12-2 Boiler 120 VAC Connections
(Refer to Electrical Schematic)
Figure 12-3 Control Module 120 VAC
Connections
12 - ELECTRICAL WIRING & CONNECTIONS