16 - TROUBLESHOOTING
Table 16-1 Alarm Codes for Service Required LED on freewatt
Control Module
ERROR
CODE
INDICATES CHECK OR REPAIR
1
THERMOSTAT COMMUNICATIONS ERROR
1. CHP MODE SWITCH IN
ON
POSITION
2. CABLES AND CONNECTIONS BETWEEN
THE THERMOSTAT AND THE HI MODULE
3. LOWER FURNACE ACCESS PANEL
INSTALLED
4. IMPROPERLY PROGRAMMED
THERMOSTAT
2
OUTDOOR SENSOR ERROR
1. CHECK OUTDOOR SENSOR AND CON-
NECTION OR INTERNAL 20k OHM DEFAULT
RESISTOR
3
MCHP COMMUNICATIONS ERROR
1. RESET SYSTEM POWER
2. POWER TO MCHP
3. CABLES AND CONNECTIONS BETWEEN
HONDA MCHP AND HI MODULE
4
MCHP DEVICE ERROR (MCHP ASSERTING “FAILURE” STATUS, IE. A HARD ERROR) CHECK HONDA MCHP DIAGNOSTICS
5
MCHP DEVICE WARNING (MCHP ASSERTING “WARNING” STATUS, IE. A SOFT ERROR)
6
freewatt
PLUS
FLASH PARAMETER INTEGRITY CHECK ERROR SERVICE REQUIRED
7
SYSTEM POWER SWITCH OFF, UNABLE TO ENTER BACKUP MODE (NOTE: NOT DEFINED IN HY-
DRONIC SYSTEM)
8
MCHP PLACED IN LOCKED MODE BY SERVICE TECH, PREVENTS MCHP OPERATION
9
RESERVED FOR FUTURE USE
10
ERROR CODE 10 NOT USED
11
LOW DWELLING TEMPERATURE. BOILER DOWN OR THERMOSTAT “OFF” BY MISTAKE
12
RESERVED FOR FUTURE USE
13
VIRTUAL WATCHDOG TIME-OUT. AN UNEXPECTED FIRMWARE EXECUTION ERROR
OCCURRED.
REPLACE CONTROLLER MODULE
14
EXHAUST GAS LEAK SENSOR FAILURE, HONDA MCHP ERROR 39.0 (EX_SENS_FAIL)
15
EXHAUST GAS LEAK SENSOR POWER FAILURE, HONDA MCHP ERROR 39.1,(EX_SENS_POWER_
FAIL)
16
EXHAUST GAS LEAK SENSOR ALARM, COMBUSTION GAS DETECTED, HONDA MCHP ERROR 10.1,
(EX_LEAKAGE_FAIL)
17
NO DC POWER SUPPLY VOLTAGE DETECTED IN BACKUP MODE. (LOAD_PWR_FAULT)
INDICATES A FAULT IN 120V LOAD
CIRCUIT
18
DETECTED A freewatt
PLUS
TRANSFER SWITCH COMMUNICATIONS FAILURE Check fTS communications cable
19
DETECTED A freewatt
PLUS
TRANSFER SWITCH DEVICE ERROR see freewatt
transfer switch IOM
20
ERROR CODE 20 NOT USED
21
DETECTED A freewatt
PLUS
TRANSFER SWITCH STATE ERROR see freewatt
transfer switch IOM
22
RESERVED FOR FUTURE USE
23
DETECTED A freewatt
PLUS
TRANSFER SWITCH CONTACTOR #1 ERROR see freewatt
transfer switch IOM
24
DETECTED A freewatt
PLUS
TRANSFER SWITCH CONTACTOR #2 ERROR see freewatt
transfer switch IOM
25
EXHAUST GAS LEAK SENSOR TEST BUTTON PRESSED
26
VOLTAGE DETECTED ON THE freewatt
PLUS
TRANSFER SWITCH ISLAND NODES (I1 OR I2) IN
BACKUP POWER MODE
see freewatt
transfer switch IOM
27
RESERVED FOR FUTURE USE
28
MISSING L1 OR L2 OF AC POWER (fTS_AC_FAULT)
BLOWN FUSE, FAULTY WIRING, UTILITY
FAULT
29-98
RESERVED FOR FUTURE USE
99
VIRTUAL WATCHDOG TIME-OUT OCCURRED 5 OR MORE TIMES. MULTIPLE UNEXPECTED FIRM-
WARE EXECUTION ERRORS OCCURRED.
REPLACE CONTROL MODULE