PART 1 – GENERAL
1.01 SUMMARY
A. Section Includes: Warm Air Micro-CHP System using fuel gas (natural gas or liquid propane) to heat indoor
spaces and generate power, while also providing on-demand power for grid boost or back-up power conditions.
System can also integrate conventional air conditioning equipment for summer time cooling operation.
B. Related Sections:
a. Other Division 23 HVAC Sections
1.E.1 1.02 REFERENCES
A. ANSI:
a. ANSI Z21.47-/CSA2.3 latest Revision: American National Standard/CSA Standard for Gas-Fired Central
Furnaces
b. 10 CFR Part 430 Method of Testing for Annual Fuel Utilization Ef ciency or Residential Central Furnaces
and Boilers
B. UL:
a. UL 2200 Standard for Stationary Engine Generator Assemblies
b. UL 1741 Standard for Inverters, Converters, Controllers and Interconnection System Equipment for Use
with Distribute Energy Resources
C. NFPA:
a. NFPA 37 Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines (2002
Edition or Latest Revision)
b. NFPA 54-2006 National Fuel Gas Code
c. NFPA 70-2005 National Electric Code
1.E.2 1.03 SYSTEM DESCRIPTION
A. Performance Requirements:
a. Furnace
i. Firing Rates: 60, 80, 100 or 120 Btu/hr
ii. Annual Fuel Utilization Ef ciency: 95%
iii. Stages of Combustion and Air Flow: Two (2)
iv. ECM Blower Motor Ef ciency: 70% or higher
v. Cooling: 1 - 5 Tons (Capability if out tted with Air Conditioning Equipment)
b. MCHP Unit
i. Steady State Ef ciency: 89% or higher
ii. Power Output:
1. MCHP Mode = 1.2 kW
2. Grid Boost Mode = 1.8 kW
3. Back-up Mode = 0.2 – 1.8 kW
iii. Noise: Under 50 dBA at 3 feet
iv. Emissions: Under 400 ppm CO and NOx
v. Grid Interconnection: Provide an MCHP unit that meets or exceeds the performance requirements outlined in
UL 1741
c. Power Management
ECR International
2201 Dwyer Avenue
Utica, NY 13501
Phone: (315) 797-1310
Fax: (315) 797-3762
Website: www.freewatt.com
Section 23 54 35
Warm Air Micro-CHP System
with Back-Up Power & Grid
Boost Capability
Guide Speci cation – WAJ Model
GUIDE SPECIFICATION
Page view 30