i. System shall optimize power output with power management equipment.
ii. Confi guration of power management equipment shall allow for pre-selected loads to have
delayable, non-delayable, interruptible and non-interruptible settings.
1.E.3 1.04 SUBMITTALS
A. General: Submit listed submittals in accordance with Conditions of Contract and Section [01 33 00 –
Submittal Procedures]
B. Product Data: Submit product data, including manufacturer’s technical specifi cation sheets and User Guides.
C. Load Calculation: Submit a residential load calculation performed by ACCA’s Manual J7.
D. Shop Drawings: Submit installation manuals for system components.
1.E.4 1.05 QUALITY ASSURANCE
A. Regulatory Requirements:
a. Furnace: Certifi ed to ANSI Z21.47/CSA 2.3 latest Revision: American National Standard/CSA Standard
for Gas-Fired Central Furnaces
d. MCHP Unit: Certifi ed to UL 2200 Standard for Stationary Engine Generator Assemblies and UL 1741
Standard for Inverters, Converters, Controllers and Interconnection System Equipment for Use with
Distributed Energy Resources
b. All system components must be approved for installation in the State of Massachusetts by the State
Plumbing Board.
B. Manufacturer Qualifi cations:
a. Minimum of 5 years experience in design and manufacture of micro-combined heat and power systems.
1.E.5 1.06 DELIVERY, STORAGE & HANDLING
A. General: Comply with Division 01 Product Requirements Section
B. Delivery: Deliver equipment in manufacturer’s original, unopened, undamaged containers with identifi cation
labels and installation/owner manuals intact.
C. Storage and Protection: Store equipment protected from exposure to harmful environmental conditions.
1.E.6 1.07 WARRANTY
A. Project Warranty: Refer to Conditions of the Contract for project warranty provisions.
B. Manufacturer’s Warranty: Submit in accordance with Section [01 78 36 – Warranties] for Owner’s acceptance
manufacturer’s standard warranty document executed by authorized company offi cial. Manufacturer’s warranty is
in addition to, and not a limitation of, other rights Owner may have under Contract Documents.
a. Warranty Period:
i. System: 24 months from the date of installation or 27 months from the date of shipment,
whichever comes fi rst.
PART 2 – PRODUCTS
2.01 WARM AIR MICRO-CHP SYSTEM
A. Manufacturer: ECR International
a. Contact: 2201 Dwyer Avenue, Utica, NY 13501; phone (315) 797-1310; fax (315) 797-3762; Website:
www.ecrinternational.com
B. Warm Air freewatt
®
PLUS System:
a. Models:
i. Natural Gas: WAJ060N00A, WAJ080N00A, WAJ100N00A, WAJ120N00A
ii. Propane: WAJ060L00A, WAJ080L00A, WAJ100L00A, WAJ120L00A
b. System shall include:
i. High-effi ciency, gas furnace (ANSI Z21.47/CSA 2.3):
GUIDE SPECIFICATION