Receiving and Transporting
10 SPDU Installation Manual
Transporting
Exercise caution. When transporting enclosures, try to avoid impact. Even the best packaging
cannot guarantee equipment protection. In addition, keep personnel clear of an enclosure in transport.
The units are heavy and can cause serious bodily injury.
Top box removal. Should the SPDU’s (and/or the sidecars) height exceed the doorway(s) by less
than 5.5 inches (14 cm), the unit’s Top Box can be removed to gain clearance. Using a large standard
screwdriver, detach the (4) silver ¼-20 x 6” bolts located at the overhead corner positions. Removing
the top box will reduce the unit’s height to 76 inches (193 cm). Once the SPDU (or sidecar) is in
position and cleared of all doorways, re-attach the top box using the same four bolts.
Storage
The SPDU is not suited for outdoor storage, and the equipment warranty may not be applicable under
such circumstances. If the equipment must be stored, it should be stored indoors and with its
protective packaging still in place.
The equipment should be kept in a climate-controlled environment with a temperature range of
0° to 40°C (32° to 104°F) and a relative humidity of 0% to 95%, non-condensing.
The equipment must be protected at all times from excessive moisture, construction dirt,
corrosive elements, and other contaminants. The enclosure (still on its pallet, if possible) should
be set on a firm and level surface.
Make sure the equipment does not exceed floor loading requirements. For size and weight
information, refer to “Product SKUs” on page 4 or “SPDU with one sidecar” on page 34.
DO NOT, under any circumstances, stack other equipment on top of the enclosure.
Note
For size and weight information, refer to “Product SKUs” on page 4 or “SPDU
with one sidecar” on page 34.
Ventilation screen
Main cable
entry plate
Knockout
plates (5)
FRONT of enclosure
REAR of enclosure
Silver BOLTS
Silver BOLT
Silver BOLT
Top Box
Page view 13