APC 220 VAC User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 13
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
Page 5
c. 2.2 kVA or 1540 W, whichever limit is reached first (for the 2.2 kVA model).
d. 3 kVA or 2100 W, whichever limit is reached first (for the 3 kVA models).
e. 5 kVA or 3500 W, whichever limit is reached first for the 5 kVA models).
f. 6 kVA or 4200 W, whichever limit is reached first (for the 6 kVA models).
g. 8 kVA or 6400 W, whichever limit is reached first (for the 8 kVA models).
h. 10 kVA or 8000 W, whichever limit is reached first (for the 10 kVA models).
i. 15 kVA or 12000 W, whichever limit is reached first (for the 15 kVA model).
j. 20 kVA or 16000 W, whichever limit is reached first (for the 20 kVA model).
2. Efficiency: The UPS full-load efficiency stated here is without degradation of
output regulation as specified:
a. Efficiency is at least 88% for the 1 kVA models.
b. Efficiency is at least 90% for the 2 kVA models.
c. Efficiency is at least 92% for the 2.2 kVA, 3 kVA, 5 kVA, 6 kVA, 8 kVA and
10 kVA models.
d. Efficiency is at least 94% for the 15 kVA and 20 kVA models.
3. Input:
a. AC Input Nominal Voltage:
1) 220/230/240 Vac, single phase, 3 wire (L + N + G), connected via IEC-320
C14 connector (1 kVA models)
2) 220/230/240 Vac, single phase, 3 wire (L + N + G), connected via IEC-320
C20 connector (2 kVA models)
3) 220/230/240 Vac, single phase, 3 wire (L + N + G), connected via IEC-320
C20 connector (3 kVA models).
4) 220/230/240 Vac, single phase, 3 wire (L + N + G), connected via hardwire
(5 kVA and 6 kVA models)
5) 220/230/240 Vac, single phase, 3 wire (L + N + G) or 380/400/415 Vac,
three phase, 5 wire (L1+L2+L3+N+G) (8 kVA,10 kVA, 15 kVA and 20 kVA
models)
b. AC Input Voltage Window:
1) For 1 kVA to 6 kVA non-marine models, 160 280 Vac (L-N) at full load,
while providing nominal charging to the battery system; or 100 280 Vac (L-
N) at 50% load, while providing nominal charging to the battery system.
2) For 8 kVA to 20 kVA non-marine models, 160 280 Vac (L-N) for single
phase input or 277 485 Vac for three phase input at full load while
providing nominal charging to the battery system.
3) For the 1 kVA and 2.2 kVA marine models, 180 V to 280 V.
4) For the 3 kVA and 6 kVA marine models, 180 V to 270 V.
c. Input Frequency Range: 45-65 Hz, auto-selecting.
d. Input Power Factor: Minimum 0.95 at 100% load at 230 Vac.
e. Input Current Distortion:
1) Maximum 6% at 100% load at 230 Vac (1 kVA, 2 kVA, 8 kVA, 10 kVA,
15 kVA, and 20 kVA models)
2) Maximum 8% at 100% load at 230 Vac (2.2 kVA 3 kVA, 5 kVA, and 6 kVA
models)
4. UPS Output:
a. AC Nominal Output Voltage: Single Phase, 3-wire (Phase + N + G)
1) 220 Vac, 225 Vac, 230 Vac, or 240 Vac, user-selectable - 1 kVA and
2 kVA models
2) 200 Vac, 208 Vac, 220 Vac, 230 Vac or 240 Vac, user-selectable - 3 kVA
to 10 kVA models
3) 220 Vac, 230 Vac or 240 Vac, user-selectable, Single Phase -15 kVA and
20 kVA models
b. Output Connectors:
1) (6) IEC 320 C13 (1 kVA and 2 kVA models)
2) (8) IEC 320 C13 and (2) IEC 320 C19 (2.2 kVA model and 3 kVA to 6 kVA
models)
3) Hardwire 3 wire (Phase + N + G), (4) IEC 320 C13 and (4) IEC 320 C19
(8 kVA and10 kVA)
4) Hardwire 3 wire (Phase + N + G), (8 ) IEC 320 C19 or Hardwire 5 wire (3
Phase + N + G), (15 kVA and 20 kVA models)
c. Output Frequency: 50/60 +/- 3 Hz tracking or 50/60 +/- 0.1 Hz tracking
(user-selectable).
Page view 4
1 2 3 4 5 6 7 8 9 10 11 12 13

Comments to this Manuals