APC BC300 Series Installation Guide Page 24

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 23
24 Installation Guide APC BC300 Series 15kW 208/450/480V UPS
990-1165
Installation
3.3.6 Communication Interface Board (Option)
Use Class 1 wiring methods.
Figure 15
14
15
2
16
17
4
18
19
6
20
21
8
13 +
25 –
"UPS on" (shown with UPS off)
"Static bypass operation" (shown with static bypass operation off)
"Battery operation" (shown with battery operation off)
"Battery low warning" (shown with "battery low" warning off)
Remote UPS shut down input (3.5 - 25 VDC pulse for 1 second minimum)
Serial Port
RS232
Serial Port
0-20 mA current loop
X003 25 PIN SUB D MALE
X004 25 PIN SUB D MALE
X005 25 PIN SUB D FEMALE
Relay Contacts: 30VAC, 60 VDC
Maximum 0.5 A, minimum 0.05 mA
X002 X001
X003X004X005
Communication
Interface Board