APC BC300 Series Installation Guide Page 36

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 35
36 Installation Guide APC BC300 Series 15kW 208/450/480V UPS
990-1165
Technical Specifications
7.2 Battery Specifications
7.3 Dimensions / Weight
15kW
Nominal DC current - Amps 75
UL rating of terminal blocks - AWG
a
a. Terminal block has two positive and two nega-
tive 8 mm (=5/16) studs, hardware provided.
Lug required.
Conductor size may vary based on installation
requirements. Size all conductors per applicable
codes.
14 - 2/0
Nominal DC voltage 216
Nominal number of cells 108
Factory-set float charge voltage
b
b. Adjust the float charge voltage setting
according to the battery manufacturers
recommendations.
246
Charger current limit - Amps
c
c. Programmable to lower level.
8
Inverter efficiency -% 100% load
75% load
50% load
25% load
90
90
88
85
BC300 Series UPS 15kW
Height 59.1 inches
Width 23.6 inches
Depth 31.7 inches
Weight (without batteries) 901 lbs
Weight (with standard internal batteries) 1237 lbs (9 minutes back-up time at 0.8 PF)
1464 lbs (15 minutes back-up time at 0.8 PF)
Page view 35
1 2 ... 31 32 33 34 35 36 37 38

Comments to this Manuals

No comments