Installation
990-1165
Installation Guide APC BC300 Series 15kW 208/450/480V UPS 7
3.1.1 UPS Footprint (measurements in inches & mm)
Figure 1
36.0
(914)
Minimum
Service
Clearance
Top View
36.0
(914)
Recommended
Cooling
Clearance
23.6
(600)
20.1
(510)
Conduit
Connection
Box
Cable Entry
19.8
(504)
27.9
(708)
31.7
(804)
Section A-A
View from inside cabinet, looking down
31.7
(804)
Side View
59.1
(1500)
Front View
AA
Notes:
1. All dimensions are in inches (millimeters).
2. Minimum cooling and service clearance 36.00 (914).
3. Conduit entry is bottom of unit.
4. Unit weight = 1BPI 1237lbs (561kg) 2BPI 1464lbs (665kg).
5. Installation must comply with all applicable national and local codes.