Installation
990-1165
Installation Guide APC BC300 Series 15kW 208/450/480V UPS 9
3.2.2 Installing Pedestals
1) Remove brackets mounted to the UPS feet during shipping
2) Lift the UPS off the floor and place the pedestals under UPS feet where the all holes of
pedestals and holes in UPS feet are aligned
3) With caution lower the UPS feet into pedestal
4) Fasten but DO NOT TIGHTEN botls, washers and nuts on the four corner feet of UPS
5) Move the UPS to the installation site
6) Tighten the bolts
3.2.3 Installing Conduit Box and Base Covers
1) Punch conduit holes in the back of the conduit box
2) Place the conduit box between the center leg and right leg of the unit, whith the open side
facing the front of the unit
3) Use four T20 torx screws and washers to fasten the conduit box to the front legs of the UPS
4) After all UPS wiring has been completed, attach conduit box cover to the front of the
conduit box
5) Use hook and loop fasteners to attach the base covers to the UPS
3.3 Installing the Maintenance Bypass Panel and UPS
Follow these guidelines when installing the Maintenance Bypass Panel and UPS:
Install the Maintenance Bypass Panel within sight of the UPS. When installing the
Maintenance Bypass Panel, see illustrations under
Wiring Diagram for BC300
and
any instructions provided with the Maintenance Bypass Panel.
Install all wiring in accordance with applicable electrical codes. Use 75° C copper
conductors.
CAUTION!
Heavy Equipment. Use caution and appropriate equipment to safely lift the UPS several inches
above the floor when installing pedestals.
NOTICE!
Place flat washer under the bolt head and the lock washer under the nut.
NOTICE!
Place flat washer, lock washer and screw in this particular order.
IMPORTANT!
If you do not have an APC Maintenance Bypass Panel, you must provide overcurrent protection
and a UPS input AC disconnect means.
APC
strongly recommends
that a means of bypassing the UPS from the critical load be
provided for maintenance.