CHAPTER 3: MENU COMMANDS
13
Setup Menu
The Setup menu lets the user customize the UPS functionality.
Menu Item Function Options
Shutdown
Sets the shutdown parameters in the event of a
utility power failure.
None
Low Batt(ery)
Dur(ation)
Sets the number of minutes an audible alarm
sounds before the UPS shuts down due to
battery exhaustion.
2(default), 5, 7, 10, 12, 15,
18, or 20 minutes
Shutdown Delay Sets the additional runtime for computer issuing
shutdown command if it needs additional time to
shut itself down.
0, 20(default), 60, 120,
240, 480, 720, or 960
seconds
Return Delay Sets the delay interval that allows utility power to
stabilize before the system goes back online
after a utility power failure.
0(default), 20, 60, 120,
240, 480, 720, or 960
seconds
Return Battery
Capacity
Sets the minimum battery capacity necessary
before repowering the load when returning from
an extended utility power failure.
0(default), 15, 25, 35, 50,
60, 75, or 90 seconds
Defaults Sets all settings to factory defaults.
Output Freq(uency) The UPS output will phase lock to the input
within this range.
50 ±3 Hz, 50 ± 0.1 Hz, 60 ±
3 Hz, 60 ± 0.1 Hz, Full
range tracking