CHAPTER 3: MENU COMMANDS
5
Powering Down the Load Equipment
Follow the steps below to turn OFF the output of the UPS and power down the load equipment.
>Control Logging
Status Display
Setup Diags
Accessories Help
Graceful Turn Off
Start Runtime Cal
>Turn UPS Output Off
Confirm:
Turn UPS OFF
NO, ABORT
> YES, Turn UPS OFF
UPS HAS BEEN
COMMANDED TO TURN
LOAD POWER OFF
UPS LOAD IS OFF
Press any key...
1. Use ‘ESC’ to view to Main Menu , and then
select CONTROL.
2. Scroll down and select the TURN UPS
OUTPUT OFF
command.
3. Confirm choice by selecting YES
.
4. You will hear some clicking sounds and see
message
.
5. In approximately 90 seconds, you will see
message
, and the green LOAD ON status
indicator will be OFF.
The output is now OFF.
6. To fully power down the UPS, turn OFF the
System Enable switch, and open the input
circuit breaker.
Comments to this Manuals