Page 22 - 6739389EN/FB
Unitary UPS (continued)
Main status bits (UPS operating information)
Normal : inverter powers load and full backup bit 4C4 = 1
time available
Danger : inverter does not power load bit 4C6 = 1
Downgraded : malfunction or environment fault bit 4C5 = 1
Load on battery : fonctionnement en autonomie bit 4C7 = 1
Normal operation
Operating modes
The following section describes the
different states of a
MGE
TM
Galaxy
TM
6000 UPS and
the addresses of the bits in the
system data array.
Normal: bit 4C4 = 1
Danger: bit 4C6 = 0
Downgraded: bit 4C5 = malfunction dependent
Load on battery: bit 4C7 = 0
Q1 closed: bit 40E = 1
Rectifier/charger on: bit 408 = 1
QF1 closed: bit 400 = 1
Inverter connected: bit 484 = 1
Q5N closed: bit 498 = 1
Q3BP open: bit 497 = 0
Q4S closed: bit 496 = 1
SS open: bit 499 = 0
K2S open (if available): bit 494 = 0
Normal: bit 4C4 = 1
Danger: bit 4C6 = 0
Downgraded: bit 4C5 = malfunction dependent
Load on battery: bit 4C7 = 1
Q1 indifferent: bit 40E = X (N/A)
Rectifier/charger off: bit 408 = 0
QF1 closed: bit 400 = 1
Inverter connected: bit 484 = 1
Q5N closed: bit 498 = 1
Q3BP open: bit 497 = 0
Q4S closed: bit 496 = 1
SS open: bit 499 = 0
K2S open (if available): bit 494 = 0
Load on battery