APC MGETM GALAXYTM 6000 User Manual Page 28

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 27
Page 28 - 6739389EN/FB
System information
Message format
This section describes the
messages exchanged between the
"GTC link" communication interface
and the external computer based
on the JBUS protocol.
The length of time after which a
message must be interpreted as
"not understood" depends on the
type of command sent.
The table opposite lists maximum
response times:
Data rate 1200 Baud 2400 Baud 4800 Baud 9600 Baud
status information only 0,5 s 0,25 s 0,12 s 0,06 s
all measurements 2 s 1 s 0,5 s 0,25 s
Response time of event (independent of data rate)
- inverter start-up and connect : 30 s
- rectifier-charger startup : 30 s
- rectifier-charger or inverter stop : 30 s
For the "responses", refer to the
"JBUS protocol" section function 1
and 3.
Example of read data array commands sent by the terminal
(address: 20H)
request station function data length CRC 16
code address
read voltage 20 03 0140 0015 82 9C
array
(21 values)
read current 20 03 0100 000F 28 03
array
(15 values)
read global 20 01 04C0 000B 7A 70
state bits
(11 bits)
command station function bit data not CRC 16
code address used
charger on 20 05 0C00 FF 00 89 DB
charger off 20 05 0C01 FF 00 D8 1B
inverter on 20 05 0C04 FF 00 C8 1A
inverter off 20 05 0C05 FF 00 99 DA
Sample commands
List of variable fields
(same for all cubicle types)
The binary data and binary
commands can be accessed bit or
word-wise.
The word address and position of
the bit in the word can be
determined from the bit address:
hundreds and tens digit of bit
address = word address;
least significant digit of bit
address = bit position.
JBUS fields address in hexadecimal access
start end
signaling 0 5 read / write
signaling 6 F read
binary data 40 BF read
commands C0 DF read / write
counters E0 FF read
currents 100 13 read
voltages 140 17 read
powers 180 19F read
frequencies 1A0 1BF read
battery 1C0 1DF read
adjustments 200 2FF read
maintenance 300 3FF read
Page view 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 37 38

Comments to this Manuals