6739389EN/FB - Page 29
System information (continued)
General definitions
object 0 1
switch open closed
unit off on
fault no fault fault
control device not activated activated
signaling units data JBUS address
hex. word
synchronisation counter 0
(MSB)
synchronisation counter ms 0 4294967295 1
(LSB)
binary times N/A 2
binary times N/A 3
binary times N/A 4
binary times N/A 5
manufacturer's ID without 1 MSB 6
model ID (MSB) without 102 LSB 6
model ID (LSB) without 54380 7
configuration 1 without N/A MSB 8
inverter type, LSB 8
same as 200
configuration 2 without hardware version MSB 9
software version LSB 9
not used A
not used B
state of equipment without same as 4E C
state of processing without same as 4C D
not used E
not used F
Signaling field
(same for all cubicle types)
measured current units JBUS address type
hex. word unitary parallel Static Switch
I1 (I phase 1) Mains 1 A 100 yes yes
I2 (I phase 2) Mains 1 A 101 yes yes
I3 (I phase 3) Mains 1 A 102 yes yes
I1 (I phase 1) inverter A 106 yes yes
I2 (I phase 2) inverter A 107 yes yes
I3 (I phase 3) inverter A 108 yes yes
I1 (I phase 1) Mains 2 A 109 yes yes
I2 (I phase 2) Mains 2 A 10A yes yes
I3 (I phase 3) Mains 2 A 10B yes yes
I1 (I phase 1) load A 10C yes yes yes
I2 (I phase 2) load A 10D yes yes yes
I3 (I phase 3) load A 10E yes yes yes
I battery A 115 bat bat
% load - 120 yes yes yes
% peak load (Ph1) - 121 yes yes yes
% peak load (Ph2) - 122 yes yes yes
% peak load (Ph3) - 123 yes yes yes
Tables of measured data
Current fields
Legend:
yes: available in this cubicle;
bat: available in this cubicle if
battery installed;
no entry: not available.