NetBotz Rack Monitor 450/550 Installation and Quick Configuration Manual8
Connect Sensors to Sensor Ports
This procedure applies to the following sensors, which are supported by the appliance and connect to the
sensor ports:
• Temperature Sensor (AP9335T)
• Temperature/Humidity Sensor (AP9335TH)
• NetBotz Vibration Sensor (NBES0306)
• NetBotz Smoke Sensor (NBES0307)
• NetBotz Spot Fluid Sensor (NBES0301)
• NetBotz 0-5 V Sensor Cable (NBES0305)
• NetBotz Door Switch Sensor for APC Racks (NBES0303)
• NetBotz Door Switch Sensor for Rooms or Third Party Racks (NBES0302)
• NetBotz Dry Contact Cable (NBES0304)
For sensors that connect to A-Link ports (Temperature Sensors with Digital Display
[AP9520T] and Temperature/Humidity Sensors with Digital Display [AP9520TH]),
see “Connect Sensors and Sensor Pods to A-Link Ports” on page 10.
Connect APC and third-party sensors to the six sensor ports labeled Sensors on the appliance.
• Third-party dry contact sensors require the NetBotz Dry Contact Cable (NBES0304). To connect
a sensor to the cable, follow the instructions provided with the sensor and the instructions
provided with the cable.
• Standard third-party 0-5 V sensors require the NetBotz 0-5 V Sensor Cable (NBES0305). To
connect a sensor to the cable, follow the instructions provided with the sensor and the instructions
provided with the cable.
• If a sensor cable is not long enough, use an RJ-45 coupling (provided with some sensors) and
standard CAT-5 cabling to extend the cable up to 15 m (50 ft) for a Temperature/Humidity Sensor
(AP9335TH) or a Temperature Sensor (AP9335T) and up to 30.5 m (100 ft) for all other
supported sensors.