USER’S GUIDE
Battery Management System
31
Reset Discharge Voltages
Reset Lowest Discharge Voltages (control console). The lowest
discharge voltage is the lowest voltage measured for each battery in a
string during discharge. To clear the stored lowest discharge voltage:
1. Select Device Manager
2. Select Reset Discharge Voltages
3. Select Reset Lowest Discharge Voltages
Reset Lowest Discharge Voltages (Web interface). Select this option
from the Detailed Status menu of the Battery Management System
menu.
Reset Charge Current Deviation Benchmark
Reset Charge Current Deviation Benchmark (control console). The
response benchmark indicates the condition of the battery and the
connections to it. It is established when the system is commissioned, when
the batteries are replaced, or after a discharge.
1. The response benchmark is automatically cleared during a discharge.
To clear the stored response benchmark value and force it to be reset,
select Device Manager
2. Select Reset Response Benchmark
3. Select Reset Lowest Response Benchmark
Reset Charge Current Deviation Benchmark (Web interface). Select
this option from the Detailed Status menu of the Battery Management
System menu.