InRow RP CW Installation14
Service access
An area of minimum 900 mm (36 in) of clear floor space in front of and behind the equipment is
recommended for service. All required normal maintenance can be performed from the front or back of
the equipment.
An area of minimum 1200 mm (48 in) of clear floor space in front of or behind the equipment is
recommended to roll the equipment out of a row.
Note: Check local and national codes and regulations for further service access requirements
Dimensions are shown in mm (in).