37InRow RP CW Installation
Communication connections
A-Link connections. The A-Link bus connection allows communication between equipment. Only
one InRow RP needs to be defined through the display. The numbering of the other equipment (up to a
maximum of twelve) will take place automatically.
To enable the equipment to work as a group, link the units using CAT-5 cables with RJ-45 connectors as
shown. Terminators must be inserted into the A-Link ports at the first and last InRow RP.
The maximum wire length for the entire group may not exceed 1000 m (3,280 ft).
A-Link IN (with provided RJ-45 terminator)
A-Link IN
InRow A-Link cable (CAT-5 ethernet cable)
A-Link OUT (with provided RJ-45 terminator)
A-Link out
na0733a
First InRow RP Second InRow RP Last InRow RP