APC ACRP500 Specifications Page 44

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 43
InRow RP CW Installation36
Water outlet temperature sensors
There are two water outlet temperature sensors, one
for top connection and one for bottom connection.
These sensors are wired to the main board on the
electrical panel. See “Main controller board” on
page 10.
The unit is delivered with top connection as the
default configuration, i.e. the wire with a green wire
tie is positioned in connector J23 (marked with green)
on the main board. If the configuration is changed
from top to bottom, switch the wire already positioned
in the connector J23 with the wire labeled with a green
and a white wire tie. This wire is part of the wire
harness inside the electrical panel.
na2263a
J23
Top connection: Wire with
green wire tie in J23
Bottom connection:
Wire with green and
white wire ties in J23