APC IN ROW RD ACRD101 Specifications Page 28

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 27
InRow Air Cooled RD Installation20
Recommended line sizes
Equivalent length
m (ft) Line type ACRD100, ACRD101 (OD)
15 (50) Discharge line (horizontal) 5/8 in ACR
Discharge line (vertical) 1/2 in ACR
Liquid line 1/2 in ACR
30 (100) Discharge line (horizontal) 5/8 in ACR
Discharge line (vertical) 1/2 in ACR
Liquid line 1/2 in ACR
46 (150) Discharge line (horizontal) 5/8 in ACR
Discharge line (vertical) 1/2 in ACR
Liquid line 1/2 in ACR
Note: All refrigerant pipes must be straight ACR to have 565 psig or above MWP.
Note: The Equivalent Length of 1/2 in OD discharge line pipe should be kept to less than
18 m (60 ft).
Note: The Total Equivalent Length of discharge line should be less than 46 m (150 ft) to
prevent an excessive hot gas pressure drop which can increase the discharge pressure
during hot summer days.
Note: To have a Total Equivalent Length of 61 m (200 ft), the load must be reduced by
5%.
Page view 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 47 48

Comments to this Manuals

No comments