InRow Air Cooled RD Installation30
Rack temperature sensor
The rack temperature sensor monitors and controls the equipment
airflow and ensures an adequate supply of cooling air to the server
racks in the data center.
The equipment is supplied with an external rack temperature
sensor. See “Install kit” on page 5. This sensor, along with wire
clamps and wire clips, are included in the installation kit shipped
with the equipment.
Installing the rack temperature sensor
Note: Rack temperature sensor installation is not required if the equipment operates in Rack
Air Containment System (RACS) or Hot Aisle Containment System (HACS) mode. The
InRow configuration requires temperature sensor installation.
1. Insert the rack temperature sensor connector in the temperature sensor port at the user interface.
See “User interface connections” on page 28.
a. For a top installation, push the rack temperature
sensor through the port located at the top of the
equipment.
b. For a bottom installation, route the sensor
through the access hole in the bottom of the
equipment.
2. Route the sensor through either the top or the bottom
of the adjacent server rack.
3. Secure the temperature sensor cable to the front door
of the adjacent server rack at multiple locations using
the provided wire clips as shown. See “Install kit” on
page 5.
Install the sensor where lack of sufficient cooling air
is most likely. The optimum position of the rack temperature sensor will vary from installation to
installation, but must be located in the airflow to allow proper readings.
Servers most likely to have insufficient or inadequately cooled air due to the recirculation of hot
air from the hot aisle include:
a. Servers positioned at the top of a rack.
b. Servers positioned at any height in the last rack at an open end of a row.
c. Servers positioned behind flow-impairing obstacles such as building elements.
d. Servers positioned in a bank of high-density racks.
e. Servers positioned next to racks with Air Removal Units (ARU).
f. Servers positioned very far from the equipment.
g. Servers positioned very close to the equipment.
gen0744a
gen0767a
Wire clip
Temperature
sensor