Apc GALAXY 7000 User Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
Layout >
34020846EN/AD - Page 13
1. Installation
1.2 Layout
Dimensions
Weights
Weight values are purely indicative.
See the packing labels for the precise weight of the equipment.
For more information on the weight of your system, see the Transport/storage/handling manual (doc. no. 34020840).
Overall dimensions H x W x D in mm
Unpacked cabinet On pallet cabinet
UPS cabinets in kVA
250 - 300 1900 x 1412 x 855 2027 x 1525 x 970
400 1900 x 1412 x 855 2027 x 1525 x 970
500 1900 x 1812 x 855 2027 x 1925 x 970
SSCs in kVA
800 1900 x 1012 x 855 2027 x 1125 x 970
1200 1900 x 1412 x 855 2027 x 1525 x 970
2000 1900 x 1412 x 855
1900 x 1012 x 855
2027 x 1525 x 970
2027 x 1125 x 970
2000 light 1900 x 1012 x 855 2027 x 1125 x 970
External bypass or SSC maintenance cabinets in kVA
800 1900 x 1012 x 855 2027 x 1125 x 970
1200 1900 x 1412 x 855 2027 x 1525 x 970
2000 1900 x 1412 x 855 2027 x 1525 x 970
Battery /auxiliary cabinets (mm width)
400 1900 x 412 x 855 2027 x 959 x 970
700 1900 x 712 x 855 2027 x 825 x 970
1000 1900 x 1012 x 855 2027 x 1125 x 970
1400 1900 x 1412 x 855 2027 x 1525 x 970
UPS cabinets SSC
Power rating in kVA 250 300 400 500 Power rating in kVA 800 1200 2000 2000 light
Max. weight in kg 960 960 1110 1470 Max. weight in kg 450 720 1430 600
External bypass cabinets or SSC maintenance
cabinets
Auxiliary cabinets (empty)
Power rating in kVA 800 1200 2000 Power rating in kVA 400 700 1000 1400
Max. weight in kg 340 450 700 Max. weight in kg 90 135 150 200