Electrical characteristics >
34020846EN/AD - Page 60
2. Appendices
Line-current values
Permissible UPS overloads as a function of time
Rated
power of
each UPS
unit
Continuous input
current at U=400V
Input current for load PF =
0.9, U = 400 V at 1.25 In
overload limited to 10 min.
Input current for load PF =
0.9, U = 400 V at 1.5 In
overload limited to 30 sec.
Input/output fuse
ratings
250 kVA 368 A 441 A 530 A 630 A
300 kVA 442 A 530 A 636 A 630 A
400 kVA 587 A 706 A 848 A 800 A
500 kVA 735 A 881 A 1058 A 1000 A
I/In
2,2
2
1,8
1,6
1,4
1,2
1
10
4
1010,1
t (s)
10
5
10
3
10
2
600
20°C 30°C 35°C 40°C
10 30