Apc SILCON 10-40KW 400V UPS User Manual Page 54

  • Download
  • Add to my manuals
  • Print
  • Page
    / 90
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 53
54 Installation Guide APC Silcon 10-40kW 400V UPS
990-4050
Options/Accessories
6.0 Options/Accessories
Please contact your local APC representative for information on options/accessories available
in your region. See “How to Contact APC” in this guide.
6.1 Service Bypass Panel for Single Operation
UPS Exter-
nal
System
Input
Fuse
[A]
Max.
Pro-
spec-
tive
Short-
Circuit
Current
[kA]
System
Input/
UPS
Input
Cable
[mm2]
**
System
Output/
UPS
Output
Cable
[mm2]
**
Max.
Exter-
nal
Syste
m
Output
Fuse
[A]***
Max.
Cable
Size/
Stud
Size
Dimensions
HxWxD [mm]
Weight
[kg]
Fixing
Cen-
tres
AxB
[mm]
10kW
20kW
40kW
20
40
80
15
15
25
4
10
25
2.5
6
16
16
32
63
16
mm2
(E:M6)
16
mm2
(E:M6)
35
mm2
(E:M6)
315x305x
125(175*)
315x305x
125(175*)
315x400x
125(175*)
7
7
11
240x
240
240x
240
270x
330
Fixing holes in rear of box
4 x ø 6.5mm:APC Service Bypass Panel
4 x ø 6.5mm:APC Service Bypass Panel
10/20kW & 40kW
60kW & 80kW
Page view 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 89 90

Comments to this Manuals

No comments