88 Installation Guide APC Silcon 10-40kW 400V UPS
990-4050
Appendix
9.0 Appendix
9.1 Table 1. Installation Planning Data
Main Input
Breaker
Field
Wiring*
Battery Bank**
UPS Module
Service Bypass Panel
Field
Wiring
Output
Breaker
*
** Internal Batteries available for 40kW units and smaller
*
*
Q1
Q2
Q3
* Not supplied by APC
Installation Planning Data
APC Silcon Series
AC Input Battery System DC AC Output
Min. Input Input Full I
Nom
I
Max
Load side Heat
Power rating Source P (kW) I (A) Cable Overcurrent V
n
load Disch Disch I
n
Overcurrent Dissipation
kW kVA Pf V Hz Nom. Max. Nom. Max. (per phase) Protection* (Vdc) P(kW) (A) (A) (A) Protection* (kW)
10 10 1 380
400
415
50/60 11.2 13.0 17.7
17.0
16.3
19.5
18.7
17.9
4mm
2
20 A 2x384 10.8 14 16 15.2
14.5
13.9
16 A 0.54
20 20 1 380
400
415
50/60 22.2 25.7 35.3
33.7
32.4
38.8
37.1
35.6
10mm
2
40 A 2x384 21.5 28 33 30.3
29.0
27.8
32 A 0.94
40 40 1 380
400
415
50/60 43.9 50.9 69.8
66.7
64.0
76.8
73.4
70.4
16mm
2
80 A 2x384 42.2 55 65 60.6
58.0
55.6
63 A 1.5
COLUMN 1a 1b 1c 1d 1e 1f 1g 1h 2a 2b 2c 2d 3a 3b 4a
NOTES 3 4 1 2 9 5, 6, 13 8 12 10 11 6, 7 13
* Provided by others
Page view 87