14 Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation 990-2282C-001
Parallel System
How to turn into external maintenance bypass
Warning: In bypass operation the batteries are still charged. If a total power off is required,
the load must be off and the batteries must be pulled out to the red disconnect line, see the
section How to perform a total power off.
From the Overview Screen, press ENTER.
Go to Control by using the UP/DOWN
navigation keys and press
ENTER.
Go to UPS into Bypass by using the UP/DOWN
navigation keys and press
ENTER.
Go to YES, UPS into Bypass by using the UP/
DOWN
navigation keys and press ENTER.
From the UPS: Check that all UPS units are in bypass on each of the displays. The yellow bypass
LED is lit on each UPS unit.
From the external Maintenance Bypass Panel (MBP): Check that the bypass lamp indicator (H3) is
lit at
Q3.
From the external MBP: Turn the bypass switch (Q3) to position “|(ON).
From the external MBP: Check that the lamp indicator of the output isolation breaker (H4) at Q4 is
lit.
From the external MBP: Turn the output isolation breaker (Q4) to position “O” (OFF). The UPS
system is now in external maintenance bypass with the batteries still powered.
Note! If you need to turn the UPS units completely OFF, proceed with steps 11–18.
From the UPS: Turn OFF each UPS unit from the display via Control Turn Load Off Yes, Tu r n
Load Off.
Chrg 100%
Load 000%
xxxVin 000Vout x0Hz
Runtime: 0hr 0m
Press
Control
Status
Setup
Logging
Display
Diags
Help
Use
Press
Diags
Control
Status
Setup
Logging
Display
Help
Press
Diags
UPS into Bypass
Do Self Test
Simulate Power Fail
Start Runtime Cal
Use
Press
Confirm:
UPS into Bypass
NO, ABORT
YES, UPS into Bypass
Use Press