990-2282C-001 Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation 19
Single and Parallel Systems
How to turn load off/on via the display interface
Warning: Disconnecting the UPS output to the load does NOT de-energize the UPS!
Always follow the total power off procedure if you need to de-energize the UPS in
emergency situations, see the section How to perform a total power off under
respectively Single System without External Bypass Panel, Single System with External
Bypass Panel and Parallel System.
Turn Load off – How to disconnect the UPS output to the load equipment.
From the Overview Screen, press ENTER.
Go to Control by using the UP/DOWN
navigation keys and press
ENTER.
Go to Turn L o ad O f f by using the UP/DOWN
navigation keys and press
ENTER.
Go to YES, Turn Load OFF by using the UP/
DOWN
navigation keys and press ENTER.
If the UPS is running in parallel operation this procedure must be carried out on each UPS.
Turn load on – How to connect the UPS output to the load equipment.
From the Overview Screen, press ENTER.
Go to Control by using the UP/DOWN
navigation keys and press
ENTER.
Chrg 100%
Load 000%
xxxVin 000Vout x0Hz
Runtime: 0hr 0m
Press
Control
Status
Setup
Logging
Display
Diags
Help
Use
Press
Diags
Control
Status
Setup
Logging
Display
Help
Press
Diags
Turn Load Off
Press
Use
Confirm:
Turn Load OFF
NO, Abort
YES, Turn Load OFF
Use
Press
Chrg 100%
Load 000%
xxxVin 000Vout x0Hz
Runtime: 0hr 0m
Press
Control
Status
Setup
Logging
Display
Diags
Help
Use
Press
Diags
Control
Status
Setup
Logging
Display
Help
Press
Diags