APC SUA2200RMI2U/KIT User Manual Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 17
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
12
PROBLEM AND/OR POSSIBLE
CAUSE
S
OLUTION
THE OVERLOAD LED IS ILLUMINATED AND THE UPS EMITS A SUSTAINED ALARM TONE
The UPS is overloaded. The
connected equipment exceeds
the “maximum load,” as de-
fined in Specifications at
www.apc.com.
The alarm remains on until the overload is removed. Disconnect nonessen-
tial equipment from the UPS.
The UPS continues to supply power as long as it is online and the circuit
breaker does not trip; the UPS will not provide power from batteries in the
event of a utility voltage interruption.
If a continuous overload occurs while the UPS is on battery, the unit turns
off output in order to protect the UPS from possible damage.
THE REPLACE BATTERY/BATTERY DISCONNECTED LED IS ILLUMINATED
This LED flashes and short
beep is emitted every two sec-
onds to indicate the battery is
disconnected.
Check that the battery connectors are fully engaged.
Weak battery. Allow the battery to recharge for 24 hours and perform a self-test. If the
problem persists after recharging, replace the battery.
Failure of a battery self-test.
This LED is illuminated and
the UPS emits short beeps for
one minute. The UPS repeats
the alarm every five hours.
Allow the battery to recharge for 24 hours and perform another self-test to
confirm the replace battery condition. If the battery passes the self-test, the
alarm will stop and the LED will clear.
If the battery fails again, it must be replaced. The connected equipment is
unaffected.
THE SITE WIRING FAULT LED ON THE REAR PANEL IS ILLUMINATED (120 V MODEL ONLY)
The UPS is plugged into an
improperly wired utility power
outlet.
Wiring faults detected include missing ground, hot-neutral polarity reversal,
and overloaded neutral circuit.
Contact a qualified electrician to correct the building wiring.
THE INPUT CIRCUIT BREAKER TRIPS
The UPS is overloaded. Reduce the load on the UPS by unplugging equipment. Reset the breaker.
THE AVR BOOST OR AVR TRIM LEDS ARE ILLUMINATED
Your system is experiencing a
period of low or high voltage.
Have qualified service personnel check your facility for electrical prob-
lems. If the problem continues, contact the utility company for further as-
sistance.
THERE IS NO UTILITY POWER
There is no utility power and
the UPS is off.
120/208/230 V models only: Use the Cold Start feature to supply power to
the connected equipment from the UPS battery.
Press the button for one second and release. The UPS will beep briefly.
Press and hold the
button again for about three seconds. The unit will
emit two beeps. Release the button during the second beep.
Page view 13
1 2 ... 9 10 11 12 13 14 15 16 17

Comments to this Manuals

No comments