APC SUA2200RMI2U/KIT User Manual Page 9

  • Download
  • Add to my manuals
  • Print
  • Page
    / 17
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 8
7
3: USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE
OR OPTIONAL SMART SLOT ACCESSORY CARDS.
FUNCTION
F
ACTORY
D
EFAULT
U
SER SELECTABLE
CHOICES
DESCRIPTION
Automatic Self-
Test
Every 14 days
(336 hours)
Every 7 days
(168 hours),
On Startup Only,
No Self-Test
Set the interval at which the UPS will
execute a self-test.
UPS ID UPS_IDEN Up to eight charac-
ters (alphanumeric)
Uniquely identify the UPS, (i.e. server
name or location) for network man-
agement purposes.
Date of Last Bat-
tery Replacement
Manufacture Date mm/dd/yy Reset this date when you replace the
battery module.
Minimum Capacity
Before Return from
Shutdown
0 percent 0, 15, 30, 45, 50, 60,
75, 90 percent
Following a low-battery shutdown, the
battery modules will be charged to the
specified percentage before powering
connected equipment.
Voltage Sensitivity
The UPS detects
and reacts to line
voltage distortions
by transferring to
battery operation to
protect connected
equipment.
High : Brightly illu-
minated - high sensi-
tivity.
: Dimly illumi-
nated - medium sen-
sitivity.
: No illumina-
tion; low sensitivity.
Adjust by pressing the voltage sensi-
tivity button
(rear panel). Use a
pointed object, (such as a pen) to do
so.
Note: In situations of poor power qual-
ity, the UPS may frequently transfer to
battery operation. If the connected
equipment can operate normally under
such conditions, reduce the sensitivity
setting to conserve battery capacity
and service life.
Alarm Delay Con-
trol
Enable Enable, Mute, Dis-
able
Mute ongoing alarms or disable all
alarms permanently.
Shutdown Delay 90 seconds 0, 90, 180, 270, 360,
450, 540, 630 sec-
onds
Set the interval between the time when
the UPS receives a shutdown com-
mand and the actual shutdown.
Page view 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Comments to this Manuals

No comments