Maintenance Bypass Panel 60kW /
Symmetra
®
PX 10 - 40 kW, 400V
990-1277
Maintenance Bypass Panel 60kW /
Symmetra
®
PX 10 - 40 kW, 400V
990-1277
Maintenance Bypass Panel60kW /
Symmetra
®
PX 10 - 40 kW, 400V
990-1277
10
How to return to On-Line from
Maintenance Bypass Operation
1) Close (turn ON) the
Q1
breaker on the Maintenance Bypass Panel.
2) Set the Symmetra PX UPS
DC Disconnect
breaker and
System Enable
switch to the ON
position.
As soon as you set the
DC Disconnect
breaker and the
System Enable
switch to the
ON position, the UPS transfers to Static Bypass (with the load supported).
3) If applicable, set the XR Battery Enclosure
DC Disconnect
breaker to ON.
The
H2
LED above the
Q2
breaker will illuminate, indicating that it is safe to
operate the
Q2
breaker.
4) Close (turn ON) the Q2 breaker on the Service Bypass Panel.
The
H3
LED above the
Q3
breaker will illuminate, indicating that it is safe to
operate the
Q3
breaker.
.
5) Open (turn OFF) the Q3 breaker on the Maintenance Bypass Panel.
As soon as you open the
Q3
breaker, the UPS will automatically return from Static
Bypass.
Service Bypass
Switch
UPS
Service Bypass
Switch
UPS
Service Bypass
Switch
UPS