CHAPTER 4: MESSAGES
17
Troubleshooting
The PowerView reports various messages on the display, including alarm status and changes in system
configuration. This section lists all the PowerView display messages, what each means, and an appropriate
corrective action.
Contact APC Technical Support Staff for assistance with complex UPS problems. Refer to the APC Web site
at http://www.apc.com/support
for a location near you.
More than one of these messages may occur at one time. If this happens, be sure to review all of the messages for a
better understanding of the system condition.
PowerView Message Meaning Corrective Action
#Pwr modules changed
since last ON.
At least one power module has been
added or removed from the UPS
since the last time the Pwr ON
command was issued.
#Batteries changed since
last ON.
At least one battery module has been
added or removed from the UPS
since the last time the Pwr ON
command was issued.
No corrective action necessary.
Proceed with the startup.
No Redundant Intelligence
Module.
There is no RIM installed. Proceed with the startup or abort
the startup and install a RIM.
Note: Without a functioning RIM,
there is no redundancy in the
event of a MIM failure.
Batt capacity less than
Return Batt Cap.
The battery capacity of the UPS is
less than the user specified minimum
battery capacity required to turn on
the load.
Option 1: Abort the startup and
allow batteries to recharge.
Option 2: Continue startup, with
less than minimum battery
capacity.
Start-Up
Input Freq outside
configured range.
The input frequency to the UPS is
outside the configured range. The
output frequency will not synchronize
with the input frequency. Normal
bypass is not available. The system
will start on-battery.
Option 1: Improve the frequency
of the incoming voltage.
Option 2: Widen the range of the
acceptable incoming frequency
with the PowerView.
(Startup>Setup>OuputFreq)
Option 3: Proceed with startup.
Normal bypass is not available
and system may start on battery
power.